5500kVA Resistive Inductive Load Bank for Generator Testing
Click image to view full size image
Product: Views:2035500kVA Resistive Inductive Load Bank for Generator Testing 
Unit price: Negotiable
MOQ:
Quantity:
Delivery date: Since the payment date Days delivery
Valid until: Long-term effective
Last updated: 2017-09-21 19:03
  Inquiry
Details

5500KVA Resistive Inductive Load Bank offers a 0.80 power factor load and is designed for testing large generators, switchgear, transformers and UPS systems. The structural skid with fork lift pockets allows for portability and is ideal for shipyards, power plants, OEMs and data centers. It is perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems where rated kVA, rated power factor and rated current testing is required.

Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment

Technical Parameters
5500kVA Resistive Inductive Load Bank for Generator Testing

Rating voltage/frequency

400VAC 3 phase 4 wire, 50Hz, phase voltage 230VAC

Max Load Power

Apparent Power: 5500kVA

Resistive Load: 4400kW; Inductive Load: 3300kvar

Load Resolution

Resistive Load: 30 steps, 1,2,2,5,10,10,20,50,100,21*200kW

Inductive Load: 25 steps, 1,2,2,5,10,10,20,50,100,100,15*200kvar

Power Factor

0.8

Load Tolerance (each step)

±5%

Load Tolerance(overall)

±3%

Fan Control Power

380VAC 3 phase 4 wire, 50Hz, phase voltage 220VAC

Wire Connection

Load bank input--Copper bar (star coupling "Y")

Control power input--Connector-bar

Communication Interface

RS485,RS232

Insulation

F

Max Protection Grade

IP55

Way of Working

Continuous Working

Cooling

Forced air cooling, horizontal inlet air, vertical exhaust cooling

Enclosure

Container type with a ladder, air inlet and outlet with mesh enclosure and protection door

Transportation

Hoisting

Color

RAL7035

Dimensions

About 6058mm*2350mm*2591mm(L×W×H)

Weight

About 25000kg

Operating Environment Parameter

Ambient Temperature

-10ºC~+50ºC

Relative Humidity

≤95%

Atmospheric Pressure

86~106kPa

Brands of Main Components

Contactor

CHINT

Fuse

DELIXI

MCU

INFINEON

Alloy Resistor

(self-developing)

Data Processing Software

 (self-developing)


Structure Chart

Application Case

Workshop

Contact Information
Bruce Pan
Hebei Kaixiang Electrical Technology Co., Ltd
 No 33 Wangshan Road, Shijiazhuang City, 
Hebei Province, China
Tel: 0086-311-85138355 Fax: 0086-311-85138330   
Cell phone: 0086-13739721527
 
 www.load-banks.com
Our service is beyond of products, but the feeling of customers
 

Inquiry